Model Item |
Specifications | ||||
---|---|---|---|---|---|
Standard model | Full Function model | Motion model | CNC motion model | ||
HX-CP1S08 | HX-CP1H16 | HX-CP1S08M | HX-CP1H16M | ||
Program capacity | 8MB | 16MB | 8MB | 16MB | |
Data memory(non-retaining) | 8MB | 16MB | 8MB | 16MB | |
Data memory(retain when outage occurs) | 0.5MB | ||||
Number of extension stages | 5 | ||||
Extended cable | 0.5m, 1m, 2m | ||||
Extension distance | Maximum 2m between bases, maximum 8m in total expansion | ||||
Number of base mounted modules | Maximum 11 units(excluding power supply modules and CPU modules) | ||||
I/O points (when using a 64-point unit) | 4,224 points | ||||
Command processing speed |
Bit operations | 1.0ns | |||
Double-precision real- number arithmetic operations |
6.6ns | ||||
Programming language | Five languages in conformance with IEC61131-3 standards (LD/FBD/SFC/IL/ST) + CFC (Continuous Function Chart) | ||||
I/O processing method | Refresh processing | ||||
Supported functions |
OPC-UA | ✔ | ✔ | ✔ | ✔ |
WebVisualization *1 | - | ✔ | - | ✔ | |
NTP(Network Time Protocol) |
✔ | ✔ | ✔ | ✔ | |
FTP(server client) | ✔ | ✔ | ✔ | ✔ | |
EtherCAT® master | ✔ | ✔ | ✔ | ✔ | |
(EtherCAT® communication cycle) |
1ms∼ | ||||
Modbus-TCP client | ✔ | ✔ | ✔ | ✔ | |
Modbus-TCP server | ✔ | ✔ | ✔ | ✔ | |
Modbus-RTU master | - | ✔ | - | ✔ | |
Modbus-RTU slave | - | ✔ | - | ✔ | |
SoftMotion | - | - | ✔ | ✔ | |
CPU redundancy | - | - | - | - | |
Standard input and output interface |
Ethernet port | ✔(2 ports) | ✔(3 ports) | ✔(2 ports) | ✔(3 ports) |
SD card slot | - | ✔ | - | ✔ | |
RS-485 serial | - | ✔ | - | ✔ | |
USB host(USB memory) | ✔ | ✔ | ✔ | ✔ | |
USB device(PC connection) |
✔ | ✔ | ✔ | ✔ | |
Calendar clock | 60 second difference in a month with built-in RTC and 25 degrees in ambient temperature | ||||
Battery(sold separately) *2 | HX-BAT(for clock IC) | ||||
Maintenance function | Self diagnosis (abnormalities of microcomputers, watch dog timers, memory, batteries, and others) |
Items | Specifications | |
---|---|---|
Ethernet port specifications |
Physical layer | 10BASE-T, 100BASE-TX |
Transmission mode | AUTO, 100 Mbps full duplex, 100 Mbps half duplex, 10 Mbps full duplex, 10 Mbps half duplex | |
Modulation method | Base band | |
Topology | Star type | |
Transmission media | Twist pair cable with shields (STP), category 5/5e or higher | |
Transmission distance | 100m | |
Supports function | EtherCAT® master, Modbus-TCP client, Modbus-TCP server, CODESYS Gateway*1, network variables, TCP/IP, UDP/IP, NTP, FTP server, http*2 |
|
USB host | Standard | USB 2.0 High Speed(480 Mbps) |
Connector | A type | |
File system | FAT32 | |
Maximum capacity | 32GB | |
Maximum capacity per file | 2GB | |
Bus power source capacity | 500mA | |
Transmission distance | 5m | |
Supported function | Program transfer, file system | |
USB device | Standard | USB 2.0 High Speed(480 Mbps) |
Connector | mini-B type | |
Transmission distance | 5m | |
Supports function | CODESYS gateway(exclusively for integrated development environment HX-CODESYS connection) | |
Serial*3 | Standard | RS-485 |
Transmission speed | 4,800 / 9,600 /19.2k / 38.4k / 57.6k / 115.2k / 230k bps | |
Communication method | 2-wire type, half duplex | |
Synchronous method | Start-stop synchronous communication | |
Maximum message length | 256 bytes(Modbus-RTU) | |
Connector | Phoenix(5pin) MC1, 5/5-G-3, 5-RN(AU) | |
Terminal resistor | 120Ω(attached) | |
Transmission distance | 1,200m | |
Error check | Vertical parity check, overrun check, framing check | |
Supports function | Modbus-RTU mater, Modbus-RTU slave, generic communications | |
SD card*3 | Standard | SD(Maximum 2GB), SDHC(2 to 32GB) |
Bus interface | Normal speed, high speed | |
Bus speed | Maximum 25 MB/s | |
Specification version | 2.00 | |
File system | FAT32 | |
Maximum capacity | 32GB | |
Maximum capacity per file | 4GB | |
Supports function | File system |