Frame 250C 300C 400C 600C 800C
TYPE Electromagnetic contactor
without enclosure
Non- reversible H250C H300C H400C H600C H800C
Reversible H250C-R H300C-R H400C-R H600C-R H800C-R
Electromagnetic starter Without enclosure Non-reversible H250C-T H300C-T H400C-T H600C-T
Reversible H250C-RT H300C-RT H400C-RT H600C-RT
With enclosure Non-reversible SH250C-T SH300C-T SH400C-T SH600C-T
Reversible SH250C-
RT
SH300C-
RT
SH400C-
RT
SH600C-
RT
Thermal overload relay TR250B-1E TR400B-1E TR600B-1E
Rated insulation voltage AC660V
Max. rated capacity of motor JIS and JEM Rated operational current (A)
AC3
200-220V 240 300 400 600 800(AC2)
380-440V 240 300 400 600 800(AC2)
500-550V 145 250 350 500
Three-phase motor (kW)
AC3 and AC2
200-220V 60 75 110 150 200(AC2)
380-440V 120 150 200 300 400(AC2)
500-550V 90 160 200 300
IEC Rated operational current (A)
AC3
220-240V 240 300 400 600 800(AC2)
380-440V 240 300 400 600 800(AC2)
500-550V 145 250 350 500
Three-phase motor (kW)
AC3
220-240V 75 90 115 160 200(AC2)
380-440V 120 150 200 300 400(AC2)
500-550V 90 160 200 300
Single-phase motor(kW) AC3
JIS, JEM and IEC
100-110V
200-220V
Inching (kW) AC4
(Inching ratio 50%, electrical life 0.1 million times)
JIS, JEM and IEC
200-240V 37 45 45 55
380-440V 45 55 55 75
Rated capacity for resistance load (A)
AC1 (Electrical life 0.5 million times)
JIS, JEM and IEC
200-240V 300 350 420 600 800
(0.1milion times)
380-440V 300 350 420 600 800
(0.1milion times)
Rated thermal current (1th) A Without enclosure 300 350 420 600 800
With enclosure 240 300 400 600
Characteristics
of
operation coil
Coil burden (max.) (V.A)
50/60Hz
Pick-up 480/480 1600/1600 1800/1800
Hold-in 9/9 10/10 14/14
Coil comsumption (W) (Mean) 8 8 13
Pick-up voltage
(% of rated voltage) (Mean)
70 70 70
Drop-out voltage
(% of rated voltage) (Mean)
45 35 35
Operating time (ms)
(reference value)
Pick-up 30-50 35-60 40-70
Drop-out 20-45 20-45 25-50
Auxiliary contact specification Number Standard 2NO2NC 3NO3NC 4NO4NC
Maximum 4NO4NC
(3NO3NC... Reversible)
Rated operational
current (A)
200-240V 2 (Twin contact)
380-440V 1 (Twin contact)
Rated themal current (A) 10 (Twin contact)
Application models With mechanical interlock
With 2E themal overload relay
With three-element themal
overload relay
With latch
DC operation
DIN rail mounting

Note

*1
The ratings of the 200V class in the parenthesis when frames 20 and 50 are provided with an enclosure.
*2
The rated thermal current applies to electromagnetic contactors.
*3
The pick-up and drop-out voltages apply to 200V 60Hz power source. In case of 50Hz, the figures for frame 8C - 125C are about 10% smaller and for frame 150C - 800C are about the same.
*4
Application of Category AC3 and AC2 to the reversible electromagnetic contactors and starters shall be limited to regular reversible operation in which a motor starts reverse rotation after it has once stopped. Category AC4 is applicable when the motor starts reverse rotation before it has completely stops.
*5
The mark (●) in the application indicates that they are standard.
*6
Operating time is a reference value where 200V 50Hz is applied to AC200V coil. Operating time varies with coil voltage, frequency and phase so it is unsuitable for timing use.
*7
Testing conditions of electrical life (Category AC3) :
The making and breaking currents and operating frequency of the electrical life are tested as shown in the right drawing according to test conditions of JIS C8201-4-1, JEM 1038 and IEC60947-4-1.
*8
Themal overload relay for 220-240V 7.5kW is TR50B-1E.
*9
The minimum rating of auxiliary contact is 48V 10mA for the single contact and 24V 10mA for the twin contact.
250C - 800C