Rating and Specifications
Frame | 80C | 100C | 125C | 150C | 200C | |||
---|---|---|---|---|---|---|---|---|
TYPE | Electromagnetic contactor without enclosure | Non- reversible | H80C | H100C | H125C | H150C | H200C | |
Reversible | H80C-R | H100C-R | H125C-R | H150C-R | H200C-R | |||
Electromagnetic starter | Without enclosure | Non-reversible | H80C-T | H100C-T | H125C-T | H150C-T | H200C-T | |
Reversible | H80C-RT | H100C-RT | H125C-RT | H150C-RT | H200C-RT | |||
With enclosure | Non-reversible | SH80C-T | SH100C-T | SH125C-T | SH150C-T | SH200C-T | ||
Reversible | SH80C- RT |
SH100C- RT |
SH125C- RT |
SH150C- RT |
SH200C- RT |
|||
Thermal overload relay | TR80B-1E | TR150B-1E | TR250B-1E | |||||
Rated insulation voltage | AC660V | |||||||
Max. rated capacity of motor | JIS and JEM | Rated operational current (A) AC3 |
200-220V | 80 | 100 | 125 | 150 | 180 |
380-440V | 80 | 100 | 125 | 150 | 180 | |||
500-550V | 72 | 72 | 72 | 80 | 145 | |||
Three-phase motor (kW) AC3 and AC2 |
200-220V | 19 | 25 | 30 | 37 | 45 | ||
380-440V | 37 | 50 | 60 | 75 | 90 | |||
500-550V | 45 | 45 | 45 | 55 | 90 | |||
IEC | Rated operational current (A) AC3 |
220-240V | 80 | 105 | 126 | 150 | 182 | |
380-440V | 80 | 100 | 125 | 150 | 180 | |||
500-550V | 72 | 72 | 72 | 80 | 145 | |||
Three-phase motor (kW) AC3 |
220-240V | 22 | 30 | 37 | 45 | 55 | ||
380-440V | 37 | 50 | 60 | 75 | 90 | |||
500-550V | 45 | 45 | 45 | 55 | 90 | |||
Single-phase motor (kW) AC3 JIS, JEM and IEC |
100-110V | — | — | — | — | — | ||
200-220V | — | — | — | — | — | |||
Inching (kW) AC4 (Inching ratio 50%, electrical life 0.1 million times) JIS, JEM and IEC |
200-240V | 13 | 13 | 15 | 22 | 30 | ||
380-440V | 19 | 19 | 22 | 30 | 37 | |||
Rated capacity for resistance load (A) AC1 (Electrical life 0.5 million times) JIS, JEM and IEC |
200-240V | 120 | 135 | 150 | 200 | 260 | ||
380-440V | 120 | 135 | 150 | 200 | 260 | |||
Rated thermal current (1th) A | Without enclosure | 120 | 135 | 150 | 200 | 260 | ||
With enclosure | 80 | 105 | 125 | 150 | 180 | |||
Characteristics of operation coil |
Coil burden (max.) (V.A) 50/60Hz |
Pick-up | 490/420 | 400/400 | 480/480 | |||
Hold-in | 50/40 | 8/8 | 9/9 | |||||
Coil comsumption (W) (Mean) | 9.5 | 7 | 8 | |||||
Pick-up voltage (% of rated voltage) (Mean) | 75 | 70 | 70 | |||||
Drop-out voltage (% of rated voltage) (Mean) | 58 | 45 | 45 | |||||
Operating time (ms) (reference value) |
Pick-up | 10-25 | 30-50 | 30-50 | ||||
Drop-out | 10-30 | 20-40 | 20-45 | |||||
Auxiliary contact specification | Number | Standard | 2NO2NC | |||||
Maximum | 4NO4NC (3NO3NC... Reversible) | |||||||
Rated operational current (A) | 200-240V | 2 (Twin contact) | ||||||
380-440V | 1 (Twin contact) | |||||||
Rated themal current (A) | 10 (Twin contact) | |||||||
Application models | With mechanical interlock | ● | ● | ● | ● | ● | ||
With 2E themal overload relay | ○ | ○ | ○ | ○ | ○ | |||
With three-element themal overload relay | ○ | ○ | ○ | ○ | ○ | |||
With latch | ○ | ○ | ○ | ○ | ○ | |||
DC operation | ○ | ○ | ○ | ○ | ○ | |||
DIN rail mounting | — | — | — | — | — |
Note