Frame 80C 100C 125C 150C 200C
TYPE Electromagnetic contactor without enclosure Non- reversible H80C H100C H125C H150C H200C
Reversible H80C-R H100C-R H125C-R H150C-R H200C-R
Electromagnetic starter Without enclosure Non-reversible H80C-T H100C-T H125C-T H150C-T H200C-T
Reversible H80C-RT H100C-RT H125C-RT H150C-RT H200C-RT
With enclosure Non-reversible SH80C-T SH100C-T SH125C-T SH150C-T SH200C-T
Reversible SH80C-
RT
SH100C-
RT
SH125C-
RT
SH150C-
RT
SH200C-
RT
Thermal overload relay TR80B-1E TR150B-1E TR250B-1E
Rated insulation voltage AC660V
Max. rated capacity of motor JIS and JEM Rated operational current (A)
AC3
200-220V 80 100 125 150 180
380-440V 80 100 125 150 180
500-550V 72 72 72 80 145
Three-phase motor (kW)
AC3 and AC2
200-220V 19 25 30 37 45
380-440V 37 50 60 75 90
500-550V 45 45 45 55 90
IEC Rated operational current (A)
AC3
220-240V 80 105 126 150 182
380-440V 80 100 125 150 180
500-550V 72 72 72 80 145
Three-phase motor (kW)
AC3
220-240V 22 30 37 45 55
380-440V 37 50 60 75 90
500-550V 45 45 45 55 90
Single-phase motor (kW) AC3
JIS, JEM and IEC
100-110V
200-220V
Inching (kW) AC4
(Inching ratio 50%, electrical life 0.1 million times)
JIS, JEM and IEC
200-240V 13 13 15 22 30
380-440V 19 19 22 30 37
Rated capacity for resistance load (A)
AC1 (Electrical life 0.5 million times)
JIS, JEM and IEC
200-240V 120 135 150 200 260
380-440V 120 135 150 200 260
Rated thermal current (1th) A Without enclosure 120 135 150 200 260
With enclosure 80 105 125 150 180
Characteristics
of
operation coil
Coil burden (max.) (V.A)
50/60Hz
Pick-up 490/420 400/400 480/480
Hold-in 50/40 8/8 9/9
Coil comsumption (W) (Mean) 9.5 7 8
Pick-up voltage (% of rated voltage) (Mean) 75 70 70
Drop-out voltage (% of rated voltage) (Mean) 58 45 45
Operating time (ms)
(reference value)
Pick-up 10-25 30-50 30-50
Drop-out 10-30 20-40 20-45
Auxiliary contact specification Number Standard 2NO2NC
Maximum 4NO4NC (3NO3NC... Reversible)
Rated operational current (A) 200-240V 2 (Twin contact)
380-440V 1 (Twin contact)
Rated themal current (A) 10 (Twin contact)
Application models With mechanical interlock
With 2E themal overload relay
With three-element themal overload relay
With latch
DC operation
DIN rail mounting

Note

*1
The ratings of the 200V class in the parenthesis when frames 20 and 50 are provided with an enclosure.
*2
The rated thermal current applies to electromagnetic contactors.
*3
The pick-up and drop-out voltages apply to 200V 60Hz power source. In case of 50Hz, the figures for frame 8C - 125C are about 10% smaller and for frame 150C - 800C are about the same.
*4
Application of Category AC3 and AC2 to the reversible electromagnetic contactors and starters shall be limited to regular reversible operation in which a motor starts reverse rotation after it has once stopped. Category AC4 is applicable when the motor starts reverse rotation before it has completely stops.
*5
The mark (●) in the application indicates that they are standard.
*6
Operating time is a reference value where 200V 50Hz is applied to AC200V coil. Operating time varies with coil voltage, frequency and phase so it is unsuitable for timing use.
*7
Testing conditions of electrical life (Category AC3) :
The making and breaking currents and operating frequency of the electrical life are tested as shown in the right drawing according to test conditions of JIS C8201-4-1, JEM 1038 and IEC60947-4-1.
*8
Themal overload relay for 220-240V 7.5kW is TR50B-1E.
*9
The minimum rating of auxiliary contact is 48V 10mA for the single contact and 24V 10mA for the twin contact.

80C - 200C