Rating and Specifications
Frame | 65C | 80C | 100C | 125C | 150C | |||
---|---|---|---|---|---|---|---|---|
TYPE | Electromagnetic starter | Without enclosure | Non-reversible | H65C-TK | H80C-TK | H100C-TK | H125C-TK | H150C-TK |
Reversible | H65C-RTK | H80C-RTK | H100C-RTK | H125C-RTK | H150C-RTK | |||
With enclosure | Non-reversible | SH65C-TK | SH80C-TK | SH100C-TK | SH125C-TK | SH150C-TK | ||
Reversible | SH65C- RTK |
SH80C- RTK |
SH100C- RTK |
SH125C- RTK |
SH150C- RTK |
|||
Thermal overload relay | TR80B-2E | TR150B-2E | ||||||
Rated insulation voltage | AC660V | |||||||
Max. rated capacity of motor | JIS and JEM | Rated operational current (A) AC3 |
200-220V | 65 | 80 | 100 | 125 | 150 |
380-440V | 65 | 80 | 100 | 125 | 150 | |||
500-550V | 52 | 72 | 72 | 72 | 80 | |||
Three-phase motor (kW) AC3 and AC2 |
200-220V | 15 | 19 | 25 | 30 | 37 | ||
380-440V | 30 | 37 | 50 | 60 | 75 | |||
500-550V | 30 | 45 | 45 | 45 | 55 | |||
IEC | Rated operational current (A) AC3 |
220-240V | 65 | 80 | 105 | 126 | 150 | |
380-440V | 65 | 80 | 100 | 125 | 150 | |||
500-550V | 52 | 72 | 72 | 72 | 80 | |||
Three-phase motor (kW) AC3 |
220-240V | 18.5 | 22 | 30 | 37 | 45 | ||
380-440V | 30 | 37 | 50 | 60 | 75 | |||
500-550V | 30 | 45 | 45 | 45 | 55 | |||
Characteristics of operation coil |
Coil burden (max.) (V.A) | Pick-up | 220/190 | 490/420 | 400/400 | |||
100V : about 1/4 | ||||||||
Hold-in | 18/14 | 50/40 | 8/8 | |||||
Coil consumption (mean) (W) | 6 | 9.5 | 7 | |||||
Pick-up voltage (% of rated voltage) | 75 | 75 | 70 | |||||
Drop-out voltage (% of rated voltage) | 58 | 58 | 45 | |||||
Operating time (ms) 200V, 50Hz (reference value) |
Pick-up | 10-20 | 10-25 | 30-50 | ||||
Drop-out | 10-30 | 10-30 | 20-40 | |||||
Auxiliary contact | Type of contacts | Twin contact | ||||||
Numbers | Standard | 2NO2NC | ||||||
Maximum | 4NO4NC(3NO3NC... Reversible) | |||||||
Mechanical interlock unit | ● | |||||||
Life (million times) | Mechanical | 5 | ||||||
Electrical | 1 | |||||||
Available voltage range of operational coil (V) | 24-550 | 100-440 |
Remarks
Rated operational current | Rated thermal currentMinimum rating | |||||
---|---|---|---|---|---|---|
AC (AC15) | DC L/R<40mn | |||||
200 - 220V | 380 - 440V | 500 -550V | 48V | 110V | ||
2A | 1A | 0.75A | 0.7A | 0.3A | 10A | 24V 10mA |
Note