AC reactor applies to harmonics suppression, when unbalance ratio of power supply voltage is over 3% and power supply capacity is over 500 kVA, on in case drastic change of power supply voltage happens. Also, it is useful for power factor improvement.
Model name | Weight (kg) | Applicable inverter capacity (kW) |
---|---|---|
ALI-2.5L2 | 2.8 | 0.2-1.5 |
ALI-5.5L2 | 4 | 2.2, 3.7 |
ALI-11L2 | 5 | 5.5, 7.5 |
ALI-22L2 | 10 | 11, 15 |
ALI-33L2 | 11 | 18.5, 22 |
ALI-50L2 | 19 | 30, 37 |
ALI-75L2 | 25 | 45, 55 |
ALI-120L2 | — | 75, 90 |
ALI-180L2 | — | 110 |
Model name | Weight (kg) | Applicable inverter capacity (kW) |
---|---|---|
ALI-2.5H2 | 2.7 | 0.4-1.5 |
ALI-5.5H2 | 4 | 2.2, 3.7 |
ALI-11H2 | 6 | 5.5, 7.5 |
ALI-22H2 | 10 | 11, 15 |
ALI-33H2 | 11.5 | 18.5, 22 |
ALI-50H2 | 19 | 30, 37 |
ALI-75H2 | 25 | 45, 55 |
ALI-120H2 | 35 | 75, 90 |
ALI-180H2 | 48 | 110, 132 |
ALI-220H2 | 48 | 160 |
ALI-300H2 | 54 | 185, 220 |