Frame 8C 10C 10B 11 12
TYPE Electromagnetic contactor without enclosure Non- reversible H8C H10C H11 H12
Reversible H10B-R H11-R H12-R
Electromagnetic starter Without enclosure Non-reversible B)H8C-T B)H10C-T B)H11-T B)H12-T
Reversible B)10B-RT B)H11-RT B)H12-
RT
With enclosure Non-reversible B)SH8C-T B)SH10C-T B)SH11-T
Reversible B)SH10B-RT B)SH11-RT
Thermal overload relay TR12B-1E
Rated insulation voltage AC660V
Max. rated capacity of motor JIS and JEM Rated operational current (A)
AC3
200-220V 11 12 12 12
380-440V 6 9 9 9
500-550V 5 8 6 8
Three-phase motor (kW)
AC3 and AC2
200-220V 2.2 2.5 2.5 2.5
380-440V 2.2 4 4 4
500-550V 2.2 4 3.7 4
IEC Rated operational current (A)
AC3
220-240V 11 12 12 12
380-440V 7 9 9 9
500-550V 5 8 6 8
Three-phase motor (kW)
AC3
220-240V 2.5 3 3 3
380-440V 3 4 4 4
500-550V 3 4 3.7 4
Single-phase motor (kW) AC3
JIS, JEM and IEC
100-110V 0.4 0.4 0.4
200-220V 0.75 0.75 0.75
Inching (kW) AC4
(Inching ratio 50%, electrical life 0.1 million times)
JIS, JEM and IEC
200-240V 0.75 1.5 1.5 1.5
380-440V 1.5 2.2 2.2 2.2
Rated capacity for resistance load (A)
AC1 (Electrical life 0.5 million times)
JIS, JEM and IEC
200-240V 20 20 18 20
380-440V 20 20 18 20
Rated thermal current (1th) A Without enclosure 20 20 18 20
With enclosure 15 15 15 15
Characteristics
of
operation coil
Coil burden (max.) (V.A)
50/60Hz
Pick-up 45/40 45/40 45/40
Hold-in 9/7 9/7 9/7
Coil comsumption (W) (Mean) 2.4 2.4 2.4
Pick-up voltage (% of rated voltage) (Mean) 65 75 68 75
Drop-out voltage (% of rated voltage) (Mean) 50 50 50 50
Operating time (ms)
(reference value)
Pick-up 10-15 10-15 10-15
Drop-out 10-30 10-30 10-30
Auxiliary contact specification Number Standard 1NO or 1NC (2NO1NC)
x 2
1NO1NC
or
2NO2NC
2NO1NC
or
1NO2NC
Maximum
Rated operational current (A) 200-240V 2 (Twin contact)
380-440V 1 (Twin contact)
Rated themal current (A) 10 (Twin contact)
Application models With mechanical interlock
With 2E themal overload relay
With three-element themal overload relay
With latch ○ (H10-L)
DC operation ○ (H10-G)
DIN rail mounting

Note

*1
The ratings of the 200V class in the parenthesis when frames 20 and 50 are provided with an enclosure.
*2
The rated thermal current applies to electromagnetic contactors.
*3
The pick-up and drop-out voltages apply to 200V 60Hz power source. In case of 50Hz, the figures for frame 8C - 125C are about 10% smaller and for frame 150C - 800C are about the same.
*4
Application of Category AC3 and AC2 to the reversible electromagnetic contactors and starters shall be limited to regular reversible operation in which a motor starts reverse rotation after it has once stopped. Category AC4 is applicable when the motor starts reverse rotation before it has completely stops.
*5
The mark (●) in the application indicates that they are standard.
*6
Operating time is a reference value where 200V 50Hz is applied to AC200V coil. Operating time varies with coil voltage, frequency and phase so it is unsuitable for timing use.
*7
Testing conditions of electrical life (Category AC3) :
The making and breaking currents and operating frequency of the electrical life are tested as shown in the right drawing according to test conditions of JIS C8201-4-1, JEM 1038 and IEC60947-4-1.
*8
Themal overload relay for 220-240V 7.5kW is TR50B-1E.
*9
The minimum rating of auxiliary contact is 48V 10mA for the single contact and 24V 10mA for the twin contact.

8C - 12