Molded Case Circuit Breakers : S Series

S-30S, S-30E, S-50E, S-50EB, S-50SB, S-60RB

Type S-30S S-30E S-50E S-50EB S-50SB S-60RB
Number of poles 2 3 2 3 2 3 2 3 2 3 2 3
Rated Current (A)
(Base ambient temperature 40℃)
3  5 10 15 20 30 3  5 10 15 20 30 5 10 15 20 30 40 50 5 10 15 20 30 40 50 5 10 15 20 30 50 5 10 15 20 30 50 60
Rated Insulation Voltage Ui (V) 500 500 500 500 690 690
Rated Impulse withstand Voltage Uimp (kV) 4 4 6 6
Rated Breaking Capacity (kA) IEC 60947-2 (Icu/Ics) AC 690V
440V 2.5 / 1 5 / 2
415V 1.5 / 1 1.5 / 1 2.5 / 1 5 / 2
400V 1.5 / 1 1.5 / 1 1.5 / 1 1.5 / 1 2.5 / 1 5 / 2
380V 1.5 / 1 1.5 / 1 2.5 / 1 5 / 2
240V 2.3 / 1.3 2.3 / 1.3 7.5 / 2 10 / 3
230V 2.5 / 1.3 5 / 2 2.3 / 1.3 5 / 2 7.5 / 2 10 / 3
DC 250V 2.5 / 1 2.5 / 1
125V 5 / 2 5 / 2
Dimensions (mm)Dimensions a 50 75 50 75 50 75 50 75 52 75 52 75
b 95 96 96 96 130 130
c 60 60 60 60 60 60
d 79 76 79 76 84 84
Net Weight (kg) 0.32 0.47 0.25 0.37 0.32 0.47 0.25 0.37 0.48 0.6 0.5 0.7
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal Front Terminal
Phase Separator for Line Side (*2)
Interior Accessories Alarm Switch AL
Auxiliary Switch AUX
Shunt Trip SHT
Undervoltage Trip UVT
Terminal Block TB
TB2
Exterior Accessories Rear-connecting Stud STB STB-2M STB-3K
(Up to 50A:STB-2M)
BSD
Flush Mounting Base Assembly GKW
(STB)
GK•GKW
(BSD)
Plug-in Mounting Base Assembly PK
Drawout Assembly PDK
Mechanical Interlock MIW MIW-2E MIW-2E
Motor-operating Mechanism MMK-S
MMK-C
MMK
Lock Cover LC LC-0B LC-03 LC-0B LC-03 LC-2G LC-2G
Handle Lock HL HL-2G HL-2G
Handle Operating Mechanism HA HA-108 HA-108
HM   HM-S12 HM-S12
Terminal Cover Front Type TMC TMC-0C TMC-0A TMC-0G TMC-0C TMC-0A TMC-0G TMC-1 TMC-1
Short Type TMC-1S TMC-1S
Long Type TMC-2D TMC-2D
Rear Type BTC BTC-1 BTC-1
IEC Rail 35 mm
Automatic Tripping Device Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic Full Magnetic
Trip Button

Note

1
● : Standard      ○ : Option
2
2-pole types marked with (*1) are supplied in 3-pole type.
3
Please state "For DC" in case of DC use . Especially, state please state kind of the power supply in case of from 30AF to 100AF.
4
Please state that number of poles of breakers when order MIW.
5
Installation of phase separators is required in case of types marked (*2).
6
The accessories marked (*3) can be installed by customers.