Hitachi

Molded Case Circuit Breakers : F Series

F-800R, FX800, F-800RH, F-1000K, F-1000C, FX1000

TYPE F-800R FX800 F-800RH F-1000K F-1000C FX1000
Numner of Poles 3 4 3 3 4 3 4 3 4 3
Rated Current (A)
(Base ambient temperature 40℃)
700 800 400 /450 / 500
600 / 700 / 800
adjustable
700 800 1000 500 / 600 / 700
800 / 900 /1000
adjustable
500 / 600 / 700
800 / 900 /1000
adjustable
Rated Insulation Voltage Ui (V) 690 690 690 690 690 690
Rated Impulse withstand Voltage Uimp (kV) 8 8 8 8 8 8
Rated
Breaking
Capacity (kA)
IEC 60947-2
(Icu/Ics)
AC 690V
440V 50 / 50 50 / 50 85 /43 85 / 22 85 / 22 85 / 85
415V 50 / 50 50 / 50 85 /43 85 / 22 85 / 22 85 / 85
400V 50 / 50 50 / 50 85 /43 85 / 22 85 / 22 85 / 85
380V 50 / 50 50 / 50 85 /43 85 / 22 85 / 22 85 / 85
240V 100 / 100 100 / 100 125 / 63 125 / 32 125 / 32 125 / 125
230V 100 / 100 100 / 100 125 / 63 125 / 32 125 / 32 125 / 125
DC 250V 40 /40 40 /40 40 / 10
125V 40 /40 40 /40 40 / 10
DimensionsDimensions a 210 280 210 210 280 210 280 210 280 210
b 274 274 274 410 410 410
c 103 103 103 150 150 150
d 141 141 141 190 190 190
Net Weight (kg) 10.5 13.5 11 10.5 13.5 26 33 26 33 26
Standard Connection Type Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal
Phase Separator for Line Side ● (*2) ● (*2) ● (*2) ● (*2) ● (*2) ● (*2)
Interior
Accessories
Alarm Switch AL ○ (*3) ○ (*3)
Auxiliary Switch AUX ○ (*3) ○ (*3)
Shunt Trip SHT ○ (*3) ○ (*3)
Undervoltage Trip UVT
Terminal Block TB
TB2
Exterior
Accessories
Rear-connecting
Stud
STB
BSD
Flush Mounting Base
Assembly
GKW(STB)
GK•GKW(BSD) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK) ○ (GK)
Plug-in Mounting
Base Assembly
PK
Drawout Assembly PDK
Mechanical Interlock MIW MIW-5 MIW-5G MIW-5 MIW-8 MIW-8 MIW-8
Motor-operating
Mechanism
MMK-S
MMK-C
MMK
Lock Cover LC
Handle Lock HL HL-6B HL-6B HL-6B
Handle Operating
Mechanism
HA HA-402 HA-402 HA-402 HA-801 HA-801 HA-801
HM HM-402 HM-407 HM-402
Terminal
Cover
Front Type TMC TMC-5D TMC-5D TMC-5D TMC-6 TMC-6 TMC-6B
Short Type
Long Type
Rear Type BTC  
IEC Rail 35 mm
Automatic Tripping Device Thermal-Magnetic Electronic Relay Thermal-Magnetic Thermal-Magnetic Electronic Relay Electronic Relay
Trip Button

Note

1
● : Standard      ○ : Option
2
2-pole types marked with (*1) are supplied in 3-pole type.
3
Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF.
4
Flush Mounting Base Assembly, GKW are standard in case of up to 250AF and FX400.
5
Please state that number of poles of breakers when order MIW.
6
Installation of phase separators is required in case of types marked (*2).
7
Tripping system of F-1000K and F-1200K are induction heat system, please state frequency when ordering.
8
For DC use, the tripping character is only instantaneous trip in case of F-1000K and F-1200K.
9
The accessories marked (*3) can be installed by customers.