F-30FB, F-60RB, F-60R, F-100S, FXK125-S, FXK125-H, F-100KB
TYPE | F-30FB | F-60RB | F-60R | F-100S | FXK125-S | FXK125-H | F-100KB | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Numner of Poles | 2 | 3 | 2 | 3 | 4 | 4 | 2(*1) | 3 | 2(*1) | 3 | 4 | |||
Rated Current (A) (Base ambient temperature 40℃) |
3 5 10 15 20 30 |
15 20 30 40 50 60 |
15 20 30 50 60 75 100 |
15 20 30 40 50 63 75 100 125 |
15 20 30 40 50 63 75 100 125 |
15 20 30 40 50 60 75 100 |
||||||||
Rated Insulation Voltage Ui (V) | 690 | 690 | 690 | 690 | 690 | |||||||||
Rated Impulse withstand Voltage Uimp (kV) | 6 | 6 | 8 | 8 | 8 | |||||||||
Rated Breaking Capacity (kA) |
IEC 60947-2 (Icu/Ics) |
AC | 690V | — | — | — | — | — | — | |||||
440V | 2.5 /1 | 10 / 10 | 10 / 5 | 30 / 30 | 50 / 50 | |||||||||
415V | 2.5 /1 | 10 / 10 | 10 / 5 | 30 / 30 | 50 / 50 | |||||||||
400V | 2.5 /1 | 10 / 10 | 10 / 5 | 30 / 30 | 50 / 50 | |||||||||
380V | 2.5 /1 | 10 / 10 | 10 / 5 | 30 / 30 | 50 / 50 | |||||||||
240V | 7.5 / 2 | 25 / 25 | 35 / 18 | 50 / 50 | 100 / 100 | 85 / 85 | ||||||||
230V | 7.5 / 2 | 25 / 25 | 35 / 18 | 50 / 50 | 100 / 100 | 85 / 85 | ||||||||
DC | 250V | 2.5 /1 | — | 5 /2 | — | — | — | 25 / 13 | — | 40 / 20 | — | — | ||
125V | 5 /2 | — | 7.5 / 2 | — | — | — | 25 / 13 | — | 40 / 20 | — | — | |||
Dimensions![]() |
a | 52 | 75 | 52 | 75 | 100 | 120 | 90 | 90 | 120 | ||||
b | 130 | 130 | 150 | 150 | 150 | |||||||||
c | 60 | 60 | 60 | 68 | 68 | 86 | ||||||||
d | 84 | 84 | 85 | 94 | 94 | 106 | ||||||||
Net Weight (kg) | 0.48 | 0.6 | 0.53 | 0.74 | 0.96 | 1.3 | 1.4 | 1.4 | 1.4 | 1.4 | 2.3 | |||
Standard Connection Type | Front Terminal | Front Terminal | Front Terminal | Front Terminal | Front Terminal | |||||||||
Phase Separator for Line Side | ○ | ● (*2) | ● | ● (*2) | ● (*2) | |||||||||
Interior Accessories |
Alarm Switch | AL | ○ | ○ | ○ | ○ | ○ (*3) | ○ | ||||||
Auxiliary Switch | AUX | ○ | ○ | ○ | ○ | ○ (*3) | ○ | |||||||
Shunt Trip | SHT | ○ | ○ | ○ | ○ | ○ (*3) | ○ | |||||||
Undervoltage Trip | UVT | — | — | ○ | — | — | ○ | |||||||
Terminal Block | TB | ○ | ○ | ○ | ○ | ○ | ||||||||
TB2 | ○ | ○ | ○ | ○ | ○ | |||||||||
Exterior Accessories |
Rear-connecting Stud |
STB | STB-2M | STB-2M | STB-1B | STB-3H (Up to 50A: STB-2D) |
STB-2S (Up to 50A) BSD-3S (60A or more) |
STB-2S (Up to 50A) BSD-3S (60A or more) |
STB-3J (Up to 50A: STB-2) |
|||||
BSD | — | — | — | — | ||||||||||
Flush Mounting Base Assembly |
GKW(STB) | ○ | ○ | ○ | — | — | ○ | |||||||
GK•GKW(BSD) | — | — | — | ○(Up to 50A) | ○ (Up to 50A) | — | ||||||||
Plug-in Mounting Base Assembly |
PK | ○ | ○ | ○ | ○(60A or more) | ○ (60A or more) | ○ | |||||||
Drawout Assembly | PDK | — | — | — | — | — | — | |||||||
Mechanical Interlock | MIW | MIW-2E | MIW-2E | MIW-1C | MIW-2C | MIW-3H | MIW-3H | MIW-3D | ||||||
Motor-operating Mechanism |
MMK-S | — | — | — | ○ | ○ | ○ | |||||||
MMK-C | — | — | — | — | — | — | ||||||||
MMK | — | — | — | — | — | — | ||||||||
Lock Cover | LC | LC-2E | LC-2E | LC-1B | LC-2C | ○ | ○ | LC-2C | ||||||
Handle Lock | HL | ○ | ○ | ○ | ○ | ○ | ○ | |||||||
Handle Operating Mechanism |
HA | HA-108 | HA-108 | HA-107 | HA-104 | — | — | HA-106 | ||||||
HM | — | HMS12 | — | HMS12 | HM-57 | — | HM-S13 | HM-S13 | HM-S11 | |||||
Terminal Cover |
Front Type | TMC | TMC-1 | TMC-1 | TMC-2C | TMC-2C | TMC-2C | TMC-3C | ||||||
Short Type | TMC-1S | TMC-1S | — | — | — | — | — | |||||||
Long Type | TMC-2D | TMC-2D | — | — | — | — | — | |||||||
Rear Type | BTC | BTC-1 | BTC-1 | BTC-2C | BTC-2C | BTC-2C | BTC-3C | |||||||
IEC Rail 35 mm | ○ | ○ | — | — | — | — | — | |||||||
Automatic Tripping Device | Full Magnetic | Full Magnetic | Full Magnetic | Thermal-Magnetic | Thermal-Magnetic | Full Magnetic | ||||||||
Trip Button | ● | ● | ● | ● | ● |
Note