Type AKS-20D AKS-20E AKS-25E AKS-32E AKS-40E AKS-40F AKS-50F AKS-40G AKS-50G AKS-63G
Ampere frame (AF) 2000 2000 2500 3200 4000 4000 5000 4000 5000 6300
Rated current
(in max) at 40℃
(A) 2000 630, 800
1000, 1250
1600, 2000
2500 3200 4000 4000 5000 4000 5000 6300
Setting current*
Control trip relay
(… × in max)
(A) (0.4 – 1.0) × in max (0.4 – 1.0) × In max (0.4 – 1.0) × In max
Rated current of neutral pole (A) 2000 630, 800
1000, 1250
1600, 2000
2500 3200 4000 4000 5000 4000 5000 6300
Rated insulation voltage (Ui) (V) 1,000 1,000 1,000
Rated operating voltage (Ue) (V) 690 690 690
Rated impulse
withstand voltage (Uimp)
(kV) 12 12 12
Frequency (Hz) 50 / 60 50 / 60 50 / 60
Number of poles (P) 3, 4 3, 4 3, 4
Rated breaking capacity(Icu)
AC 50 / 60Hz
(kA sym) IEC 60947-2
JISC 8201-2-1
220V / 230V / 380V / 415V 70 85 100 120
460V / 480V / 500V 70 85 100 120
550V / 600V / 690V 65 85 85 100
Rated service
breaking capacity (Ics)
(kA) …% × Icu 100% 100% 100% 100%
Rated making capacity
AC 50 / 60Hz (Icm)
(kA peak) IEC 60947-2
JISC 8201-2-1
220V / 230V / 380V / 415V 154 187 220 264
460V / 480V / 500V 154 187 220 264
550V / 600V / 690V 143 187 187 220
Rated shot-time
withstand current (Icw)
(kA) 1 sec 65 85 85 100
2 sec 55 75 75 90
3 sec 50 65 65 85
Operating time (ms) Maximum total breaking time 40 40 40 40
Maximum closing time 80 80 80 80
Life cycle (time) Mechanical Without maintenance 20,000 15,000 10,000 10,000
With maintenance 30,000 20,000 15,000 15,000
Electrical Without maintenance 5,000 5,000 2,000 2,000
With maintenance 10,000 10,000 5,000 5,000
Connections**   Draw-out / Fixed Horizontal connection
Vertical connection
Front connection
Mixed connection
Weight (3P / 4P) (kg) Draw-out type Main body
(With cradle)
Motor charging type 70 / 85 87 / 103 104 / 147 145 / 173 181 / 223 186 / 230
Manual charging type 68 / 83 85 / 101 102 / 145 143 / 171 179 / 221 184 / 228
Cradle only 33 / 40 44 / 50 58 / 70 78 / 90 97 / 117 102 / 124
Fixed type Motor charging type 38 / 47 44 / 55 63 / 100 76 / 94 98 / 123 103 / 130
Manual charging type 36 / 45 42 / 53 61 / 98 74 / 92 96 / 121 101 / 128
External dimensions
(H x W x D)
Dimensions
(mm) Draw-out type 3P 430 x 334 x 375 430 x 412 x 375 460 x 629 x 375 460 x 785 x 375
4P 430 x 419 x 375 430 x 527 x 375 460 x 799 x 375 460 x 1,015 x 375
Fixed type 3P 300 x 300 x 295 300 x 378 x 295 300 x 597 x 295 300 x 751 x 295
4P 300 x 385 x 295 300 x 493 x 295 300 x 767 x 295 300 x 981 x 295
Trip relay N, A, P type N, A, P type N, A, P type N, A, P type
Certificate & Approval KEMA KEMA KEMA KEMA

Note

*
Refer to trip relay specification.
**
●: Standard, ○: Option