Type | AKN-06D | AKN-08D | AKN-10D | AKN-13D | AKN-16D | ||||
---|---|---|---|---|---|---|---|---|---|
Ampere frame (AF) | 630 | 800 | 1000 | 1250 | 1600 | ||||
Rated current (in max) at 40℃ |
(A) | 200 400 630 |
400 630 800 |
1000 | 1250 | 1600 | |||
Setting current* Control trip relay (… × in max) |
(A) | (0.4 – 1.0) × in max | |||||||
Rated current of neutral pole | (A) | 400 630 |
400 630 800 |
1000 | 1250 | 1600 | |||
Rated insulation voltage (Ui) | (V) | 1,000 | |||||||
Rated operating voltage (Ue) | (V) | 690 | |||||||
Rated impulse withstand voltage (Uimp) |
(kV) | 12 | |||||||
Frequency | (Hz) | 50 / 60 | |||||||
Number of poles | (P) | 3, 4 | |||||||
Rated breaking capacity(Icu) AC 50 / 60Hz |
(kA sym) | IEC 60947-2 JISC 8201-2-1 |
220V / 230V / 380V / 415V | 65 | |||||
460V / 480V / 500V | 65 | ||||||||
550V / 600V / 690V | 50 | ||||||||
Rated service breaking capacity (Ics) |
(kA) | …% × Icu | 100% | ||||||
Rated making capacity AC 50 / 60Hz (Icm) |
(kA peak) | IEC 60947-2 JISC 8201-2-1 |
220V / 230V / 380V / 415V | 143 | |||||
460V / 480V / 500V | 143 | ||||||||
550V / 600V / 690V | 105 | ||||||||
Rated shot-time withstand current (Icw) |
(kA) | 1 sec | 50 | ||||||
2 sec | 42 | ||||||||
3 sec | 36 | ||||||||
Operating time | (ms) | Maximum total breaking time | 40 | ||||||
Maximum closing time | 80 | ||||||||
Life cycle | (time) | Mechanical | Without maintenance | 20,000 | |||||
With maintenance | 30,000 | ||||||||
Electrical | Without maintenance | 5,000 | |||||||
With maintenance | 10,000 | ||||||||
Connections** | Draw-out / Fixed | Horizontal connection | ● | ||||||
Vertical connection | ○ | ||||||||
Front connection | ○ | ||||||||
Mixed connection | ○ | ||||||||
Weight (3P / 4P) | (kg) | Draw-out type | Main body (With cradle) |
Motor charging type | 63 / 74 | ||||
Manual charging type | 61 / 72 | ||||||||
Cradle only | 29 / 32 | ||||||||
Fixed type | Motor charging type | 34 / 44 | |||||||
Manual charging type | 32 / 42 | ||||||||
External dimensions (H x W x D) ![]() |
(mm) | Draw-out type | 3P | 430 x 334 x 375 | |||||
4P | 430 x 419 x 375 | ||||||||
Fixed type | 3P | 300 x 300 x 295 | |||||||
4P | 300 x 385 x 295 | ||||||||
Trip relay | N, A, P type | ||||||||
Certificate & Approval | KEMA |
Note