Type AKH-40G AKH-50G AKH-63G
Ampere frame (AF) 4000 5000 6300
Rated current
(in max) at 40℃
(A) 4000 5000 6300
Setting current*
Control trip relay
(… × in max)
(A) (0.4 – 1.0) x In max
Rated current of neutral pole (A) 4000 5000 6300
Rated insulation voltage (Ui) (V) 1,000
Rated operating voltage (Ue) (V) 690
Rated impulse
withstand voltage (Uimp)
(kV) 12
Frequency (Hz) 50 / 60
Number of poles (P) 3, 4
Rated breaking capacity(Icu)
AC 50 / 60Hz
(kA sym) IEC 60947-2
JISC 8201-2-1
220V / 230V / 380V / 415V 150
460V / 480V / 500V 150
550V / 600V / 690V 100
Rated service
breaking capacity (Ics)
(kA) …% × Icu 100%
Rated making capacity
AC 50 / 60Hz (Icm)
(kA peak) IEC 60947-2
JISC 8201-2-1
220V / 230V / 380V / 415V 330
460V / 480V / 500V 330
550V / 600V / 690V 220
Rated shot-time
withstand current (Icw)
(kA) 1 sec 100
2 sec 100
3 sec 100
Operating time (ms) Maximum total breaking time 40
Maximum closing time 80
Life cycle (time) Mechanical Without maintenance 10,000
With maintenance 15,000
Electrical Without maintenance 2,000
With maintenance 5,000
Connections**   Draw-out / Fixed Horizontal connection
Vertical connection
Front connection -
Mixed connection -
Weight (3P / 4P) (kg) Draw-out type Main body
(With cradle)
Motor charging type 181 / 223
Manual charging type 179 / 221
Cradle only 97 / 117
Fixed type Motor charging type 98 / 123
Manual charging type 96 / 121
External dimensions
(H x W x D)
Dimensions
(mm) Draw-out type 3P 460 x 785 x 375
4P 460 x 1,015 x 375
Fixed type 3P 300 x 751 x 295
4P 300 x 981 x 295
Trip relay N, A, P, S type
Certificate & Approval KEMA

Note

*
Refer to trip relay specification.
**
●: Standard, ○: Option