Control circuit terminals Terminal arrangement

Control circuit terminals Terminal arrangement

Example of control terminal wiring (Sink Logic)

Wiring sample of control logic terminal (source logic)

Note

*
This is in case frequency reference is given with voltage input. In case to use analog current input, configuration with switch on PCB is needed.
*
When to connect relay on intelligent output terminal, please install rectifier to absorb surge in parallel to that relay. Output circuit may be damaged with surge voltage when relay is turned on and off.

Switching logic of intelligent input terminal

Factory default of intelligent input terminal is sing logic. In order to switch to source logic, remove short bar on "P24" and "PLC" of control terminal and bridge between "PLC" and "L".

Sink logic
Sink logic

Source logic
Source logic

Description of Control Terminals

analog

Power Supply
Mark Terminal Name Description Specifications
L GND for input signals Sum of internal power supply,
   digital input, and analog input and output
-
H +10V analog reference DC 10V power supply to be used to give frequency reference by variable ohm resistor to terminal O Max.10mA output
Frequency Reference
Mark Terminal Name Description Specifications
O/OI Frequency reference terminal (analog voltage input) to be set with SW on PCB To be used to give frequency reference with DC0to10V voltage input Input impedance to10kΩ Allowable input range 0 to +10VDC
Frequency reference terminal (analog current input) to be set with SW on PCB To be used to give frequency reference with 0to20mA current input. Parameter configuration with keypad is needed to use in 4-20mA mode. Input impedance to 250Ω Allowable input range 0 to 20mA

digital

Power Supply
Mark Terminal Name Description Specifications
L GND for input signals Sum of internal power supply, digital input, and analog input and output -
P24 +24V for logic inputs DC 24V power supply for digitalinput (common when source input) Max.100mA output
PLC Intelligent input common Sink logic : bridge to P24
Source logic : bridge to L Remove when to supply externally
-
Input(Discrete)
Mark Terminal Name Description Specifications
5
4
3
2
1
Intelligent input terminals 5 functions out of 35 are to be assigned on 1-5 terminal. Both sink and source logic available. Voltage between each input and PLC ON voltage min. 18V OFF voltage MAX.3V Maximum voltage 27VDC Load current 5mA(24V)
Output(Open collector)
Mark Terminal Name Description Specifications
11 Intelligent output terminals Function out of 28 is to be assigned. Open collector output between 11-CM2 terminal voltage drop when ON: less than 4V Maximum voltage 27V Maximum current 50mA
CM2 GND for intelligent output Common to intelligent output 11 terminal Maximum current 100mA
Output(Relay)
Mark Terminal Name Description Specifications
AL0
AL1
AL2
Intelligent output terminals One function out of 28 is to be assigned as C contact output. Maximum Contact Capacity AL1-AL0:AC250V, 2A(resistive load ), 0.2A(induction load) AL2-AL0: AC250V, 1A(resistive load), 0.2A(induction load) Minimum Capacity AC100V, 10mA DC5V, 100mA
Output(Pulse)
Mark Terminal Name Description Specifications
FM Digital output terminals Pulse frequency MAX.3.6kHz DC10V output Maximum current 2mA