Model L700/SJ700B- 110LFF 150LFF 185LFF 220LFF 300LFF 370LFF 450LFF 550LFF 750LFF
Enclosure *1 IP20
Applicable motor (4-pole, kW(HP)) *2 11(15) 15(20) 18.5(25) 22(30) 30(40) 37(50) 45(60) 55(75) 75(100)
Output Ratings Rated capacity
(KVA)
200V 15.2 20.0 26.3 29.4 39.1 49.5 59.2 72.7 93.5
240V 18.2 24.1 31.5 35.3 46.9 59.4 71.0 87.2 112.2
Rated output current (A) 44 58 73 85 113 140 169 210 270
Overload capacity (output current) 120%,60sec
Rated output voltage *3 3-phase (3-wire) 200 to 240V (corresponding to input voltage)
Input Rating Rated input voltage (V) 3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
Braking Dynamic braking (Short-time) *4 Built-in BRD circuit (optional resistor) External dynamic braking unit(option)
Minimum value of resistor (Ω) 10 10 7.5 7.5 5 -
Vibration *5 5.9m/s2(0.6G), 10~55Hz 2.9m/s2(0.3G), 10~55Hz
Integrated EMC filter Built-in (EN61800-3 category C3)
Zero-phase Reactor Built-in
Weight (lbs.) 6(13.2) 6(13.2) 14(30.8) 14(30.8) 14(30.8) 22(48.4) 30(66) 30(66) 43(94.6)
*1
The protection method conforms to JIS C 0920(IEC60529).
*2
The applicable motor refers to Hitachi standard 3-phase motor (4-pole).
To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3
The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4
Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5
Conforms to the test method specified in JIS C 60068-2-6:2010(IEC 60068-2-6:2007).