相数 | 単相 | 三相 | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
定格電圧(V) | 6,600 | 3,300 | 210 | 6,600 | 3,300 | 3,150 | 440 | 420 | 210 | |
定 格 容 量 (kVA) |
10 | 1.52 | 3.03 | 47.6 | 0.875 | 1.75 | 1.83 | 13.1 | 13.7 | 27.5 |
20 | 3.03 | 6.06 | 95.2 | 1.75 | 3.50 | 3.67 | 26.2 | 27.5 | 55.0 | |
30 | 4.55 | 9.09 | 143 | 2.62 | 5.25 | 5.50 | 39.4 | 41.2 | 82.5 | |
50 | 7.58 | 15.2 | 238 | 4.37 | 8.75 | 9.16 | 65.6 | 68.7 | 137 | |
75 | 11.4 | 22.7 | 357 | 6.56 | 13.1 | 13.7 | 98.4 | 103 | 206 | |
100 | 15.2 | 30.3 | 476 | 8.75 | 17.5 | 18.3 | 131 | 137 | 275 | |
150 | 22.7 | 45.5 | 714 | 13.1 | 26.2 | 27.5 | 197 | 206 | 412 | |
200 | 30.3 | 60.6 | 952 | 17.5 | 35.0 | 36.7 | 262 | 275 | 550 | |
300 | 45.5 | 90.9 | 1,430 | 26.2 | 52.5 | 55.0 | 394 | 412 | 825 | |
500 | 75.8 | 152 | 2,380 | 43.7 | 87.5 | 91.6 | 656 | 687 | 1,370 | |
750 | ― | 65.6 | 131 | 137 | 984 | 1,030 | 2,060 | |||
1,000 | ― | 87.5 | 175 | 183 | 1,310 | 1,370 | 2,750 | |||
1,500 | ― | 131 | 262 | 275 | 1,970 | 2,060 | 4,120 | |||
2,000 | ― | 175 | 350 | 367 | 2,620 | 2,750 | 5,500 | |||
2,500 | ― | 219 | 437 | 458 | 3,280 | 3,440 | 6.870 | |||
3,000 | ― | 262 | 525 | 550 | 3,940 | 4,120 | 8,250 |
単相 = 定格容量(kVA)/定格電圧(V) ×103(A)
三相 = 定格容量(kVA)/(定格電圧(V) ×ルート3)×103(A)
(銘板には上記計算式により算出した値の有効数字4桁目を四捨五入し3桁で表示します。
なお1,000Aを越すものについては桁目が“0”となります。)