Skip to main content

Hitachi

Hitachi Industrial Equipment Systems Co., Ltd.

Frame 65C 80C 100C 125C 150C
TYPE Electromagnetic starter Without enclosure Non-reversible H65C-TK H80C-TK H100C-TK H125C-TK H150C-TK
Reversible H65C-RTK H80C-RTK H100C-RTK H125C-RTK H150C-RTK
With enclosure Non-reversible SH65C-TK SH80C-TK SH100C-TK SH125C-TK SH150C-TK
Reversible SH65C-
RTK
SH80C-
RTK
SH100C-
RTK
SH125C-
RTK
SH150C-
RTK
Thermal overload relay TR80B-2E TR150B-2E
Rated insulation voltage AC660V
Max. rated capacity of motor JIS and JEM Rated operational current (A)
AC3
200-220V 65 80 100 125 150
380-440V 65 80 100 125 150
500-550V 52 72 72 72 80
Three-phase motor (kW)
AC3 and AC2
200-220V 15 19 25 30 37
380-440V 30 37 50 60 75
500-550V 30 45 45 45 55
IEC Rated operational current (A)
AC3
220-240V 65 80 105 126 150
380-440V 65 80 100 125 150
500-550V 52 72 72 72 80
Three-phase motor (kW)
AC3
220-240V 18.5 22 30 37 45
380-440V 30 37 50 60 75
500-550V 30 45 45 45 55
Characteristics
of
operation coil
Coil burden (max.) (V.A) Pick-up 220/190 490/420 400/400
100V : about 1/4
Hold-in 18/14 50/40 8/8
Coil consumption (mean) (W) 6 9.5 7
Pick-up voltage (% of rated voltage) 75 75 70
Drop-out voltage (% of rated voltage) 58 58 45
Operating time (ms) 200V, 50Hz
(reference value)
Pick-up 10-20 10-25 30-50
Drop-out 10-30 10-30 20-40
Auxiliary contact Type of contacts Twin contact
Numbers Standard 2NO2NC
Maximum 4NO4NC(3NO3NC... Reversible)
Mechanical interlock unit
Life (million times) Mechanical 5
Electrical 1
Available voltage range of operational coil (V) 24-550 100-440

Remarks

*1
Rating of Auxiliary Contact
Rated operational current Rated thermal currentMinimum rating
AC (AC15) DC L/R<40mn
200 - 220V 380 - 440V 500 -550V 48V 110V
2A 1A 0.75A 0.7A 0.3A 10A 24V
10mA
*2
The ratings of Max rated capacity of motor are in the parenthesis are provided with an enclosure.
*3
The pick-up and drop-out voltage apply to 200V, 60Hz power source. In case of 50Hz, the figures for frame 8C-125C are about 10% smaller and figures for frame 150C-600C are about the same.

Note

*1
Application of Category AC3 and AC2 to the reversible electromagnetic starters shall be limited to regular reversible operation in which a motor starts reverse rotation after it has once stopped. Category AC4 is applicable when the motor starts reverse rotation before it has completely stops. And the contactors used for reversible operation, they must be electrically interlocked using by mutual NC auxiliary contacts.
*2
Since Operating time depends on coil voltage, frequency or phase etc. the starters must not be applied for timing use.
*3
* : Thermal overload relay for 220 - 240V 7.5kW is TR50B-2E.

Product Inquiry