Hitachi

Molded Case Circuit Breakers : L Series

L-50E, L-100E, L-225E, L-400E, L-600E, L-800E

Type L-50E L-100E L-225E L-400E L-600E L-800E
Number of poles 3 4 3 4 3 4 3 4 3 4 3 4
Rated Current (A)
(Base ambient temperature 40℃)
5 10 15 20 30 50 15 20 30 50 60 75 100 125 150 175 200 225 250 300 350 400 500 600 700 800
Rated Insulation Voltage Ui (V) 690 690 690 690 690 690
Rated Impulse withstand Voltage Uimp (kV) 8 8 8 8 8 8
Rated Breaking Capacity (kA) IEC 60947-2 (Icu/Ics) AC 690V
440V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
415V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
400V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
380V 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32 125 / 32
240V 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88
230V 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88 175 / 88
DC 250V
125V
Dimensions (mm)Dimensions a 90 120 90 120 140 185 140 185 210 280 210 280
b 150 150 257 257 274 274
c 103 103 103 103 103 103
d 123 123 133 133 141 141
Net Weight (kg) 2.0 2.5 2.0 2.5 5.2 7.0 6.1 8.2 10.0 13.0 10.5 13.5
Standard Connection Type Front Terminal Front Terminal Front Terminal Front Bar Terminal Front Bar Terminal Front Bar Terminal
Phase Separator for Line Side (*2) ● (*2) ● (*2) ● (*2) ● (*2) ● (*2) ● (*2)
Interior Accessories Alarm Switch AL
Auxiliary Switch AUX
Shunt Trip SHT
Undervoltage Trip UVT
Terminal Block TB
TB2
Exterior Accessories Rear-connecting Stud STB
BSD
Flush Mounting Base Assembly GKW(STB)
GK•GKW(BSD) ○ (GK) ○ (GK) ○ (GK) ○ (GK)
Plug-in Mounting Base Assembly PK
Drawout Assembly PDK
Mechanical Interlock MIW MIW-3E MIW-3E MIW-5D MIW-5D MIW-5 MIW-5
Motor-operating Mechanism MMK-S
MMK-C
MMK
Lock Cover LC LC-2C LC-2C
Handle Lock HL HL-5 HL-5 HL-6B HL-6B
Handle Operating Mechanism HA HA-106 HA-106 HA-405 HA-405 HA-402 HA-402
HM HM-S11 HM-S11 HM-405 HM-405 HM-402 HM-402
Terminal Cover Front Type TMC TMC-3C TMC-3C TMC-5B TMC-5B TMC-5D TMC-5D
Short Type
Long Type
Rear Type BTC BTC-3C BTC-3C BTC-5B BTC-5B
IEC Rail 35 mm
Automatic Tripping Device Full Magnetic Full Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Trip Button

Note

1
● : Standard      ○ : Option
2
Please state "For DC" in case of DC use. Especially, state please state kind of the power supply in case of from 30 to 100AF.
3
Please state that number of poles of breakers when order MIW.
4
Installation of phase separators is required in case of types marked (*2).
5
The accessories marked (*3) can be installed by customers.