Hitachi

  • UVT is a device which makes ACB tripped automatically to prevent the accident on load side due to under volrage or power breakdown. There are two types, Instantaneous type and time delay type.
  • It can be installed on the rail or to the cradle.
  • Instantaneous type: only available with UVT coil.
  • Time delay type: available by connecting UVT coil and UVT time delay controller.
  • Common use for the all types.

UVT Time Delay Controller

1. The rated voltage and characteristics of UVT time delay controller

Rated voltage[Vn] Operating voltage range[V] Power consumotion[VA or W] Trip time[ms]
DC[V] AC[V] Pick up Drop out Inrush Steady-state
48–60 48 0.65–0.85Vn 0.4–0.65Vn 200 5 0.5, 1, 1.5, 3
100–130 100–130
200–250 200–250
380–480
  • Note) 0perating voltage range is the min. rated standard for each rated voltage (Vh).

2. Wiring

UVT Time Delay Controller Wiring