  • It is a control device which close a circuit breaker, when the voltage is applied continuously or instantaneously over 200ms to the coil terminals (C1, C2).

1. Rated voltage and characteristics of Closing coil

Rated voltage[Vn] Operating voltage range[V] Power consumotion[VA or W] Trip time[ms]
DC[V] AC[V] Inrush Steady-state
24–30 0.75–1.1Vn 200 5 Less
than
80ms
48–60 48 0.75–1.1Vn
100–130 100–130 0.75–1.1Vn
200–250 200–250 0.75–1.1Vn
380–480 0.75–1.1Vn
  • Note) Operating voltage range is the min. rated voltage standard for each rated voltage (Vn).

2. Specification of the wire

  • Refer to the below table regarding the length and specification of wire when using trip coil with DC 24–30 [V] or DC/AC 48–60 [V] of rated voltage.

The maximum wire length

  Rated voltage [Vn]
DC 24–30 [V] DC/AC 48 [V]
Wire type #14 AWG(2.08mm2) #16 AWG(1.31mm2) #14 AWG(2.08mm2) #16 AWG(1.31mm2)
Operating
voltage
100% 95.7m 61m 457.8m 287.7m
85% 62.5m 38.4m 291.7m 183.2m

Wiring Diagram

Wiring Diagram

  • *The dotted line to be made by the customer