Terminal Description

Terminal Symbol

Terminal Symbol Terminal Name
L1, L2, N/L3 Main power supply input terminals
U/T1, V/T2, W/T3 Inverter output terminals
+1,+ DC reactor connection terminals
+ - External braking unit connection terminals
Ground connection terminal Ground connection terminal

Screw Diameter and Terminal Width

Model Screw diameter (mm) Terminal width W (mm)
002~004NFU2/SFEF2 M3.5 7.1 Screw Diameter and Terminal Width
007~022NFU2, 037LFU2 M4 9.2
005~022SFEF2
004~040HFU2/HFEF2
005~075LFU2/HFU2/HFEF2 M5 12

Terminal arrangements

X200-002SFEF2~004SFEF2
X200-002NFU2~004NFU2
X200-005SFEF2~022SFEF2
X200-007NFU2~022NFU2, 037LFU2~075LFU2
X200-004HFEF2~075HFEF2
X200-004HFU2~075HFU2

Terminal arrangements1

Terminal arrangements2

Control circuit terminals

Terminal arrangement

Terminal arrangement

Terminal function

Input / monitor signals
Terminal name Description Ranges and Notes
AM Voltage analog output 0 to10V DC, 1mA max.
L Common for inputs
P24 +24V power for inputs 24V DC, 100mA max.
PCS Intelligent input common
5 Intelligent (programmable) input terminals, selection from:
FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input), STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.), UDC(Remote-controlled data clearing), OPE(Operator control), ADD(Frequency setpoint), FTM(Force terminal enable), RDY(Quick start enable), S-ST(Special-Set 2nd Motor Data), EMR(Emergency stop) or NO(Not selected).
Ranges and Notes
Operated by closing switch. (Input logic is selectable)
4
3
2
1
Freqency setting
Terminal name Description Ranges and Notes
H +10V analog reference Description
If no input termilal is assigned to [AT](analog input selection), the inverter outputs sum of O(voltage) and OI(current) frequency.
Assign [AT] for input terminal to selecting frequency source from voltage or current.
10V DC, 10mA max
O Analog input, voltage 0 to 10V DC,
input impedance10kohm
OI Analog input, current 4 to 20mA DC,
input impedance 250ohm
L Common for inputs
Output signals
Terminal name Description Ranges and Notes
11 Intelligent (programmable) output terminals, selection from:
RUN(run signal), FA1(Frequency arrival type 1 -constant speed), FA2(Frequency arrival type 2 -over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(Feedback voltage comparison), NDc(Network Disconnection), LOG(Logic operation result), ODC(Option Card Detection signal), LOC(Low Load Detection).
Open collector output
L level at operation (ON)
27V DC, 50mA max.
CM2 Common for intelligent output terminals
Relay output
Terminal name Description Ranges and Notes
AL2 Relay contact (alarm output)
terminals (programmable,
function is selectable same as
intelligent output terminals).
Relay contact
<Initial setting>
Normal: AL0-AL1 closed
Trip/Power OFF: AL0-AL2 closed
AC250V 2.5A
(Resistive load)
0.2A (cos =0.4)
DC30V 3.0A
(Resistive load)
0.7A (cos =0.4)
(minimum)
AC100V 10mA
DC 5V 100mA
AL1
AL0