| Terminal Symbol | Terminal Name |
|---|---|
| L1, L2, N/L3 | Main power supply input terminals |
| U/T1, V/T2, W/T3 | Inverter output terminals |
| +1,+ | DC reactor connection terminals |
| + - | External braking unit connection terminals |
| Ground connection terminal |
| Model | Screw diameter (mm) | Terminal width W (mm) | |
|---|---|---|---|
| 002~004NFU2/SFEF2 | M3.5 | 7.1 | |
| 007~022NFU2, 037LFU2 | M4 | 9.2 | |
| 005~022SFEF2 | |||
| 004~040HFU2/HFEF2 | |||
| 005~075LFU2/HFU2/HFEF2 | M5 | 12 | |
| X200-002SFEF2~004SFEF2 X200-002NFU2~004NFU2 |
X200-005SFEF2~022SFEF2 X200-007NFU2~022NFU2, 037LFU2~075LFU2 X200-004HFEF2~075HFEF2 X200-004HFU2~075HFU2 |
|---|---|
|
|

| Terminal name | Description | Ranges and Notes |
|---|---|---|
| AM | Voltage analog output | 0 to10V DC, 1mA max. |
| L | Common for inputs | — |
| P24 | +24V power for inputs | 24V DC, 100mA max. |
| PCS | Intelligent input common | — |
| 5 | Intelligent (programmable) input terminals, selection from: FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input), STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.), UDC(Remote-controlled data clearing), OPE(Operator control), ADD(Frequency setpoint), FTM(Force terminal enable), RDY(Quick start enable), S-ST(Special-Set 2nd Motor Data), EMR(Emergency stop) or NO(Not selected). |
![]() Operated by closing switch. (Input logic is selectable) |
| 4 | ||
| 3 | ||
| 2 | ||
| 1 |
| Terminal name | Description | Ranges and Notes | |
|---|---|---|---|
| H | +10V analog reference | ![]() If no input termilal is assigned to [AT](analog input selection), the inverter outputs sum of O(voltage) and OI(current) frequency. Assign [AT] for input terminal to selecting frequency source from voltage or current. |
10V DC, 10mA max |
| O | Analog input, voltage | 0 to 10V DC, input impedance10kohm |
|
| OI | Analog input, current | 4 to 20mA DC, input impedance 250ohm |
|
| L | Common for inputs | — | |
| Terminal name | Description | Ranges and Notes |
|---|---|---|
| 11 | Intelligent (programmable) output terminals, selection from: RUN(run signal), FA1(Frequency arrival type 1 -constant speed), FA2(Frequency arrival type 2 -over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(Feedback voltage comparison), NDc(Network Disconnection), LOG(Logic operation result), ODC(Option Card Detection signal), LOC(Low Load Detection). |
Open collector output L level at operation (ON) 27V DC, 50mA max. |
| CM2 | Common for intelligent output terminals | — |
| Terminal name | Description | Ranges and Notes | |
|---|---|---|---|
| AL2 | Relay contact (alarm output) terminals (programmable, function is selectable same as intelligent output terminals). ![]() <Initial setting> Normal: AL0-AL1 closed Trip/Power OFF: AL0-AL2 closed |
AC250V 2.5A (Resistive load) 0.2A (cos =0.4) DC30V 3.0A (Resistive load) 0.7A (cos =0.4) (minimum) AC100V 10mA DC 5V 100mA |
|
| AL1 | |||
| AL0 | |||
Product Inquiry