Standard specifications 200V

Model (SJH300-□□□) 2.5LF 3.5LF 5.5LF 8LF 11LF 16LF 22LF
Enclosure *1 IP20(NEMA1)
Rated capacity (kVA) 200V 2.5 3.6 5.7 8.3 11 15.9 22.1
240V 3.1 4.3 6.8 9.9 13.3 19.1 26.6
Rated input voltage 3-phase-(3-wire)200-240V(±10%),50Hz/60Hz
Rated output voltage *2 3-phase(3-wire)200-240V(Corresponding to input voltage)
Rated input current (A) 7.5 10.5 16.5 24 32 46 64
Control method Line to line sine wave pulse-width modulation(PWM) control
Output frequency range *3 0.1~1,500Hz
Frequency accuracy Digital:±0.01% of the maximum frequency, Analog:±0.2%(25±10°C)
Frequency resolution Digital setting: 0.01Hz, Analog setting: (Maximum frequency) /4,000
V/f characteristics V/f optionally variable, V/f control (constant torque, reduced torque)
Overload capacity 150% for 60sec., 200% for 0.5sec.
Acceleration/deceleration time 0.01-3,600sec.(Liner/curve, accel./decel. Selection), two-stage accel./decel.
Braking Dynamic braking(Short-time) *4 Built-in BRD circuit(optional resistor) External dynamic braking unit(option)
DC braking Performs at start ; under set frequency at deceleration, via an external input(braking force, time, and operating frequency)
Input signal Frequency setting Operator Up and down keys
External signal DC0-10V, -10(input impedance 10kO), 4~20mA(input impedance100O)
External port RS-485 interface
Forward/reverse
Start/stop
Operator Run key/Stop key(change FW/RV by function command)
External signal FW RUN/STOP(NO contact), RV set by terminal assignment(NO/NC), 3-wire input available
External port RS-485 interface
Inteligent
input
terminals
[8 terminals options]
RW(Reverse), CF1-CF4(Multispeed command), DB(External DC braking), 2~5 motor constants setting(SET0~SET2), 2CH(Second accel./Decel.)FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), STP(3-wire stop), F/R(3-wire fwd./rev.), UP/DWN(Remote-contorolled accel./decel.), UDC(Remote-controlled data clearing), SF1-SF7(Multispeed bit command 1-7), OLR(Overload limit change), NO(Not selected)
Thermistor input One terminal(PTC characteristics)
Output signal Inteligent output terminals (5 Open collector outputs, one relay NO-NC combined contact)
(Selection from run, frequency arrival, over set frequency and alarm signal)
Inteligent monitor output terminals Analog voltage, analog current, PWM output
Display monitor Output frequency, output current, scaled value of output frequency, trip history, I/O terminal condition, input power, output voltage
Other user-settable parameters V/f free-setting, frequency upper/lower limit, frequency jump, accel/decel. curve selection, manual torque boost value and frequency adjustment, analog meter tuning, start frequency, electronic thermal protection level, external start/end, analog input selection, retry after trip, reduced voltage soft start, overload restriction
Protective functions *5 Over-current, overload, braking resistor overload, over-voltage, EEPROM error, under-voltage error, CT(Current transformer) error, CPU error, external trip, USP error, ground fault, input over-voltage, instantaneous power failure, expansion card 1 error, expansion card 2 error, inverter thermal trip, phase failure detection, IGBT error, thermistor error
Environmental conditions Ambient operating/storage temperture(*6)/humidity -10~50°C/-20~65°C/20~90%RH(No condensation)
Vibration *7 5.9m/s2(0.6G),10~55Hz
Location Altitude 1,000m or less, indoors(no corrosive gases or dust) *8
Color Gray
Options Braking resistor, dynamic braking units, AC reactor, DC reactor, noise filters for inverters control devices, SJ-DG(digital input expansion card)
Operators OPE-S(4-digit LED),
OPE-SR(4-digit LED with potentiometer)(Japanese/English overlay), SRW-0J(new remote operator)
ICS-1(1m), ICS-3(3m)(Cable for oprators)
Weight kg (lbs.) 3.5 3.5 3.5 3.5 5 5 12

Standard specifications 400V

Model (SJH300-□□□) 2.5HF 3.5HF 5.5HF 8HF 11HF 16HF 22HF
Enclosure *1 IP20(NEMA1)
Rated capacity (kVA) 400V 2.6 3.6 5.9 8.3 11 15.9 22.1
480V 3.1 4.4 7.1 9.9 13.3 19.1 26.6
Rated input voltage 3-phase-(3-wire)200-240V(±10%),50Hz/60Hz
Rated output voltage *2 3-phase(3-wire)200-240V(Corresponding to input voltage)
Rated input current (A) 3.8 5.3 8.6 12 16 23 32
Control method Line to line sine wave pulse-width modulation(PWM) control
Output frequency range *3 0.1~1,500Hz
Frequency accuracy Digital:±0.01% of the maximum frequency, Analog:±0.2%(25±10°C)
Frequency resolution Digital setting: 0.01Hz, Analog setting: (Maximum frequency)/4,000
V/f characteristics V/f optionally variable, V/f control (constant torque, reduced torque)
Overload capacity 150% for 60sec., 200% for 0.5sec.
Acceleration/deceleration time 0.01-3,600sec.(Liner/curve, accel./decel. Selection), two-stage accel./decel.
Braking Dynamic braking(Short-time) *4 Built-in BRD circuit (optional resistor) External dynamic braking unit (option)
DC braking Performs at start ; under set frequency at deceleration, via an external input(braking force, time, and operating frequency)
Input signal Frequency setting Operator Up and down keys
External signal DC0-10V, -10(input impedance 10kO), 4~20mA(input impedance100O)
External port RS-485 interface
Forward/reverse
Start/stop
Operator Run key/Stop key(change FW/RV by function command)
External signal FW RUN/STOP(NO contact), RV set by terminal assignment(NO/NC), 3-wire input available
External port RS-485 interface
Inteligent
input
terminals
[8 terminals options] 
RW(Reverse), CF1-CF4(Multispeed command), DB(External DC braking), 2~5 motor constants setting(SET0~SET2), 2CH(Second accel./Decel.)FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), STP(3-wire stop), F/R(3-wire fwd./rev.), UP/DWN(Remote-contorolled accel./decel.), UDC(Remote-controlled data clearing), SF1-SF7(Multispeed bit command 1-7), OLR(Overload limit change), NO(Not selected)
Thermistor input One terminal(PTC characteristics)
Output signal Inteligent output terminals (5 Open collector outputs, one relay NO-NC combined contact)
(Selection from run, frequency arrival, over set frequency and alarm signal)
Inteligent monitor output terminals Analog voltage, analog current, PWM output
Display monitor Output frequency, output current, scaled value of output frequency, trip history, I/O terminal condition, input power, output voltage
Other user-settable parameters V/f free-setting, frequency upper/lower limit, frequency jump, accel/decel. curve selection, manual torque boost value and frequency adjustment, analog input selection, retry after trip, reduced voltage soft start, overload restriction
Protective functions *5 Over-current, overload, braking resistor overload, over-voltage, EEPROM error, under-voltage error, CT(Current transformer) error, CPU error, external trip, USP error, ground fault, input over-voltage, instantaneous power failure, expansion card 1 error, expansion card 2 error, inverter thermal trip, phase failure detection, IGBT error, thermistor error
Environmental conditions Ambient operating/storage temperture (*6) /humidity -10~50°C-20~65°C/20~90%RH(No condensation)
Vibration *7 5.9m/s2(0.6G)、10~55Hz
Location Altitude 1,000m or less, indoors(no corrosive gases or dust) *8
Color Gray
Options Braking resistor, dynamic braking units, AC reactor, DC reactor, noise filters for inverters control devices, SJ-DG(digital input expansion card)
Operators OPE-S(4-digit LED),
OPE-SR(4-digit LED with potentiometer)(Japanese/English overlay), SRW-0J(new remote operator)
ICS-1(1m), ICS-3(3m)(Cable for oprators)
Weight kg (lbs.) 3.5 3.5 3.5 3.5 5 5 12
*1
The protection method conforms to JEM1030
*2
The output voltage decreases as the main power supply voltage decreases.
*3
To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*4
Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5
High speed motor can not be protected by thermal relay.
Please use current sensor.(eg. Omron K2CM-Q or equivalent one).
*6
Storage temperture refers to the temperature in transportation.
*7
Conforms to the test method specified in JIS C 60068-2-6:2010(IEC 60068-2-6:2007).
*8
In case the inverter is used in dusty place, we recommend to use a varnish-coated inverter. Please contact us in advance.
*9
Conforms to UL and CE on insulating distance.