Jump to the main text

Hitachi Industrial Equipment Systems Co.,Ltd.

Hitachi

Power
Source
Rated
input
voltage
1-phase 200-240V +/−10%, 50/60Hz +/−5%
3-phase (200V) 200-240V +/−10%, 50/60Hz +/−5%
3-phase (400V) 380-480V +/−10%, 50/60Hz +/−5%
Applicable motor 0.2 - 7.5kW
Output frequency range 0.5 - 400Hz
Starting torque 200% or greater (at 1Hz)
(3.7kW and above : 180% or greater)
Braking torque Dynamic brake
(capacitor feedback)
20 - 50%
DC brake Variable operating frequency, time, and braking force
Overload capacity 150%, 60sec.
Acceleration/deceleration time 0.01-3,000sec.
Multispeed operation Max. 16-stage
Analog input for frequency control 0-10VDC, 4-20mA
Protective funcitons Over current protection, overload protection, braking resistor overload, over voltage protection, EEPROM error, under-voltage error, CPU error, external trip, USP, ground fault, input over-voltage protection, inverter thermal trip, gate array error and thermistor
Other functions AVR function, V/f characteristic selection, accel/
decel curve selection, frequency upper/lower limit, PID control, frequency jump, accel./decel. curve selection, external frequency input bias start/end, jogging, retry after trip, restart after instantaneous power failure, various signal outputs, overload restriction, automatic torque boost, cooling fan On/Off and trip history.
Environmental
Conditions
Ambient operating temperature −10 to 50 degrees C *
Humidity 20 to 90%RH (No condensation)
Location Less than 1,000m of altitude, indoors (no corrosive gas nor dust)
*
See derating data and carrier frequency adjustment in instruction manual when ambient operating temperature is 40°C or over.

Product Inquiry