Error Codes

Name Cause(s) Display on digital
operator
Display on remote
operator/copy unit
Over current The inverter output was short-circuited, or the motor shaft is locked or has a heavy
load. These conditions cause excessive current for the inverter, so the inverter
output is turned OFF.
While at constant speed E01 OC.Drive
During
deceleration
E02 OC.Decel
During
acceleration
E03 OC.Accel
Others E04 Over.C
Overload
protection *1
When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF
its output.
E05 Over.L
Braking resistor overloadWhen the regenerative braking resistor exceeds the usage time allowance or sage ratio, the inverter
trips and turns OFF its output to the motor.
E06 OL.BRD
Over voltage protection When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. E07 Over.V
EEPROM error *2,3 When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter
trips and turns OFF its output to the motor.
E08 EEPROM
Under-voltage error A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition
can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its
output.
E09 Under.V
CPU error A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the
motor.
E11 CPU
E22 COMM.ERR
External trip A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns
OFF the output to the motor.
E12 EXTERNAL
USP *4 When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips and does not go into Run Mode until the error is
cleared.
E13 USP
Ground fault *5 The inverter is protected by the detection of ground faults between the inverter output and the motor
during powerup tests. This feature protects the inverter, and does not protect humans.
E14 GND.Flt
Input over-voltage When the input voltage is higher than the specified value, it is detected 100 seconds after powerup
and the inverter trips and turns OFF its output.
E15 OV.SRC
Inverter thermal trip When the inverter internal temperature is above the threshold, the thermal sensor in the inverter
module detects the excessive temperature of the power devices and trips, turning the inverter output
OFF.
E21 OH FIN
Gate array error An internal inverter error has occurred in communications between the CPU and gate array IC. E23 GA
Thermistor When a thermistor is connected to terminals [PTC] and [CM1] and the inverter has sensed the
temperature is too high, the inverter trips and turns OFF the output.
E35 TH
Communications error The inverter's watchdog timer for the communications network has timed out. E60 COMM
*1
Reset operations acceptable 10 seconds after the trip.
*2
If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct.
*3
EEPROM error may occer at power-on after shutting down the power while copying data with remote operator or initializing data. Shut down the power after completing copy or initialization.
*4
USP error occures at reseting trip after under-voltage error (E09) if USP is enabled. Reset once more to recover.
*5
Ground fault error (E14) cannot be released with resetting. Shut the power and check wiring.