Rated
input
voltage
1-phase
3-phase (200V) 200-240V +/−10%, 50/60Hz
3-phase (400V) 380-480V +/−10%, 50/60Hz
Applicable motor 1.5-132kW
Output frequency range 0.1-400Hz
Starting torque 100% or greater (Torque boost mode)
Continuous operating torque
speed range
Braking torque Dynamic brake
(capacitor feedback)
DC brake Variable operating frequency, time, and braking force
Overload capacity 120%, 60sec., 150%, 0.5sec.
Acceleration/deceleration time 0.01-3,600sec.
Multispeed operation Max. 16-stage (Bit command also available)
Analog input
for frequency control
0-10VDC, 4-20mA, -10 to +10VDC.
Protective funcitons Over-current protection, overload protection, braking resistor overload protection, over-voltage protection, EEPROM error, under-voltage error, CT(Current transformer) error, CPU error, external trip, USP error, ground fault, input over-voltage protection, instantaneous power failure, option 1 connection error, option 2 connection error, inverter thermal trip, phase failure detection, IGBT error, thermistor error
Other functions V/f free-setting (up to 7 points), frequency upper/lower limit, frequency jump, accel./decel. curve selection, manual torque boost value and frequency adjustment, analog meter tuning, starting frequency, carrier frequency, electronic thermal protection level, external frequency output zero/span reference, external frequency input bias start/end, analog input selecction, retry after trip, reduced voltage soft start, overload restriction, automatic energy-saving
Environmental
Conditions
Ambient operating temperature -10 to 40 °C *
Humidity 25 to 90%RH(No condensation)
Location When using the inverter from 40°C to 50°C ambient, the output current of the inverter must be derated.
*
See derating data and carrier frequency adjustment in instruction manual when ambient operating temperature is 40°C or over.